MENU

10KW-40KW energy storage system air-cooled chiller

System Introduction

The air-cooled chiller is an integrated product developed by our company specifically for heat dissipation in the energy storage (such as battery) industry.

The applicable scenarios are as follows:

The batteries inside the energy storage container generate a lot of heat.
The equipment inside the energy storage container is sensitive to environmental temperature.


System principle

The air-cooled chiller consists of a refrigeration system and a coolant circulation system, and the system principle is shown in the figure:

a.jpg

Compressor: responsible for compressing the refrigerant and providing power for the refrigerant system.

Condenser: Designed with a parallel flow microchannel heat exchanger, it has high heat transfer efficiency, and the refrigerant condenses and releases heat in the condenser.

Condenser fan: centrifugal fan is used to provide high static pressure and large air volume, which is responsible for discharging the heat released by the refrigerant in the condenser to the outside.

Throttling element: Electronic expansion valve is used to control the refrigerant flow rate through adjustment.

Plate heat exchanger: The plate heat exchanger is the intersection of the refrigeration cycle system and the coolant cycle system, responsible for the heat exchange between the refrigerant and the coolant.

Circulating water pump: responsible for conveying coolant and providing power for the coolant circulation system.

Electric heating: responsible for heating the coolant.


Parameters of air-cooled chillers

Model

CY-ESSC10

CY-ESSC15

CY-ESSC40

Rated Voltage(V)

380AC±15﹪

380AC±15﹪

380AC±15﹪

Rated frequency(Hz)

50/60±2﹪

50±2﹪

50±2﹪

Cooling capacity(KW)

10.0

15.2

45.6

Heating load(KW)

2.0

6.5

6.5

Rated power(KW) W15/L35

3.1

6.6

20.5

Rated current(A)W15/L35

4.7

11.5

24.5

Refrigerant

R134a/1.8kg

R407C/4.5kg

R407C/8.0kg

Circulating water volume

60L/min

500L/min

500L/min

Coolant

50% ethylene glycol aqueous solution

50% ethylene glycol aqueous solution

50% ethylene glycol aqueous solution

Working Ambient Temperature

-30℃~+55℃

-30℃~+55℃

-30℃~+55℃

Water inlet and outlet method

Top inlet and outlet water

Top inlet and outlet water

Top inlet and outlet water

IP grade

IP20

IP20

IP20

Weight

140Kg

500Kg

540Kg

Overall dimensions(W*D*H)

1190mm*350mm*1100mm

995mm*995mm*2200mm

995mm*995mm*2200mm




Equipment Outline Drawing

b.jpg

10KW air-cooled chiller

c.jpg

15KW-40KW air-cooled chiller